Unit place:
Tens place
Hundreds place
Thousands place
P2.06
P2.07
If the parameter to be displayed has proportion relation with a physical value in the stopping display
parameter defined by P2.03, P2.06 can be used to designate the physical value as the display
benchmark, and P2.07 can be used to set the coefficient of the display benchmark.
When the proportion display parameter is set (i.e. P2.07≠0), the physical value will be automatically
added into the displayed parameter group in stopping status and can be viewed by pressing >>key. At
this time, there are 5 display parameters. The LEDs for the newly added parameter are LED A and LED V,
both of which shall be on.

6.4 Startup/stop Parameter (Group P3)

P3.00
Different startup modes can be adopted for different applications.
0: The inverter begins to run from the startup frequency P3.03 and accelerates to the setting frequency
after the startup frequency retention time P3.04. If the motor is still rotating upon the startup of the
inverter, the motor will be automatically decelerated to low speed before the acceleration.
1: DC current is injected first to perform DC magnetizing and DC braking on the motor. The volume and
time for the DC injection are set by P3.01 and P3.02. After the DC injection time expires, the inverter
begins to run from the startup frequency P3.03 and accelerates to the setting frequency after the startup
frequency retention time P3.04.
2: Catch a spinning motor.
The inverter will automatically identify the speed of the motor and directly start from the identified
frequency. The current and voltage are smooth without any impact during the startup.
Note: During the DC current supply, the operation panel displays "−dc−".
E5−H High Performance Universal Inverter
Display of operation panel
0: Reference frequency (Hz) ;
2: AI1 (V) ;
4: Reserved;
6: External counts
8: Close loop reference (%);
A: Reserved;
C: Reserved;
E: Reserved;
Same as above
Same as above
Same as above
Stop proportion display benchmark
Stop proportion display coefficient
Startup mode
Chapter 6 Parameter Description
User Manual
1: Bus voltage (V) ;
3: AI2 (V) ;
5: Reserved;
7: Motor rotation speed (rpm);
9: Close loop feedback (%);
B: Reserved;
D: Reserved;
F: Reserved
0~F(0)
0.0~655.35% (0.00%)
0~2(0)
63