codes of the two inverters for upload and download (d1.09) are consistent.
The copy function can be completed only when the inverter is completely powered off and
then powered up after the download of the parameters for copy is completed.

6.13 Communication Parameters (Group PC)

PC.00
PC.01
PC.02
The inverter supports international Modbus RTU protocol. Refer to the appendix.A.
PC.00 determines communication baud rate ranging from 4800~57600bps.
4: 4800bps
5: 9600bps
6: 19200bps
7: 38400bps
8: 57600bps
PC.01 sets communication format, odd−even check.
0: 1−8−1 format, without check.
1: 1−8−1 format, even check.
2: 1−8−1 format, odd check.
PC.02 sets the local address. 0 is the broadcast address, available address "1~247", 248~255 for
reservation.

6.14 Reserved

6.15 Failure Record Parameters (Group d0)

d0.00
d0.01
d0.02
d0.03
d0.04
d0.05
The inverter can record the latest three fault' code serial numbers (see 7.1 list of failure and alarm
information) and bus voltage, output current and operation frequency during failures recently occurred for
the ease of Trouble Shooting and repair.
Note: Upon the under−voltage display (LU), the parameters of fault type and failure time will not be
saved.
d0.06
d0.07
E5−H High Performance Universal Inverter
Communication baud rate
Data format
Local address
Fault type record 2
Fault type record 1
(Latest) Fault type record 0
Bus voltage of the latest failure
Actual current of the latest failure
Operation frequency of the latest failure
Total power-up time of inverter
Total operation time of inverter
Chapter 6 Parameter Description
User Manual
4~8(6)
0~2(0)
1~247(1)
0~62(0)
0~62(0)
0~62(0)
0~999V (0V)
0.0~999.9A (0.0A)
0.00~300.00 Hz (0.00Hz)
0.000~65.535 kh(0.000kh)
0.000~65.535 kh(0.000kh)
101