Multi−Section Parameter (Group P4) - V&T E5-H Series User Manual

High performance universal inverter
Table of Contents

Advertisement

P3.11
P3.12
P3.13
P3.11 is the frequency set for jog operation.
Jog acceleration time P3.12: The time from zero to maximum frequency.
Jog deceleration time P3.13: The time from maximum frequency to zero.
When the inverter is in standby status, it can adopt jog operation. The jog operation command may come
from the operation panel, multi−functional terminal or host computer.
6.5 Multi−section Parameter (Group P4)
P4.00
P4.01
P4.02
P4.03
P4.04
P4.05
P4.06
P4.07
P4.08
It is to determine the different V/F curves .
Output voltage
Output voltage
Straight line
Straight line
Figure 6−11 V/F curve
E5−H High Performance Universal Inverter
Output frequency
Output frequency
Figure 6−10 Forward/reverse dead zone time
Jog frequency
Jog acceleration time
Jog deceleration time
V/F curve reference
V/F frequency value F0
V/F voltage value V0
V/F frequency value F1
V/F voltage value V1
V/F frequency value F2
V/F voltage value V2
V/F frequency value F3
V/F voltage value V3
1.2-power
1.2-power
1.4-power
1.4-power
1.6-power
1.6-power
1.8-power
1.8-power
2-power
2-power
Output frequency
Output frequency
Chapter 6 Parameter Description
User Manual
0.10~300.00 Hz (5.00Hz)
0.1~60.0 s(6.0s)
0.1~60.0 s(6.0s)
0.00~300.00 Hz(0.00Hz)
0.0~100.0 %(0.0%)
0.00~300.00 Hz(0.00Hz)
0.0~100.0 %(0.0%)
0.00~300.00 Hz(0.00Hz)
0.0~100.0 %(0.0%)
0.00~300.00 Hz(0.00Hz)
0.0~100.0 %(0.0%)
Output voltage
Output voltage
Figure 6−12 Multi−section V/F curve
Time
Time
0~6(0)
Output frequency
Output frequency
65