2.12 Main Circuit Wiring

2.12

Main Circuit Wiring

This section gives information about the functions, specifications, and procedures necessary to safely and
correctly wire the main circuit in the drive.
NOTICE: Damage to Equipment. Do not energize and de-energize the drive more frequently than one time each 30 minutes. If
you frequently energize and de-energize the drive, it can cause drive failure.
Note:
Soldered wire connections can become loose over time and cause unsatisfactory drive performance.

Motor and Main Circuit Connections

WARNING! Electrical Shock Hazard. Do not connect terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, -, +1, +2, +3, B1, or B2 to
the ground terminal. If you connect these terminals to earth ground, it can cause damage to the drive or serious injury or death.
Note:
The location of terminals are different for different drive models.
A - DC bus terminal
B - Connect to the drive ground terminal.
C - Ground the motor case.

Configuration of Main Circuit Terminal Block

Refer to the following figure for the configuration of the main circuit terminal arrangement.
2003 to 2033, 4002 to 4018
2047, 4024, 4031
74
Figure 2.72 Wiring the Main Circuit and Motor
Model
2060, 2075
4039
4045
2088
4060
D - Three-Phase Motor
E - Use R, S, T for input power supply.
F - Input Protection (Fuses or Circuit Breakers)
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Diagram
Figure 2.73
Figure 2.74
Figure 2.75
Figure 2.76
Figure 2.77
Figure 2.78
Figure 2.79