Modbus Connection; Modbus Checklist - wtw DIQ/S 182-MOD System Operating Manual

Modular measuring system for 2 digital sensors with modbus rtu/rs 485 output
Table of Contents

Advertisement

System 182
ba75504e07
04/2012
7

Modbus connection

Note
Further instructions for the installation and operation of a Modbus
network are given in the Internet under www.modbus.org. Especially
recommendable is the "Aufbaurichtlinie (installation guideline)
PROFIBUS/FMS" , issued by the PROFIBUS user organization PNO,
(PNO order number 2.111) with many practical installation tips that
apply to Modbus systems as well.
7.1

Modbus checklist

The following checklist supports you when planning, projecting and
installing a Modbus plant with the IQ S
operation, you should be able to answer all questions with "Yes".
 Is the [bus system] (bus segment) installed without branch lines?
 Was the correct Modbus cable used (cord type A according to
EN 50170)?
 Are the poles of the signal lines A line and B line correctly connected
at all bus connections?
 Is it guaranteed that there is no short-circuit between A line, B line
and cable shielding?
 Is the shielding installed free of interruptions?
 Are the guidelines for shielding and grounding being observed, and
doesn't any unallowed potential equalization current flow
via the shielding?
 Is the maximum cable length (per bus segment) observed for the
corresponding baud rate?
 Do all devices support the required baud rate?
 Are exactly two terminators switched on at the ends of the [bus
system] (bus segment)?
 Are the terminators supplied with voltage so the following applies:
U
- U
> + 500 mV?
B line
A line
 Do all devices have individual bus addresses?
 After changing the bus address, have the devices been restarted
(switched off and on again)?
Note: The DIQ/S 182-MOD does not have to be restarted.
 Do the addresses projected in the master correspond to the actual
addresses?
 After commissioning:
Do all devices signal error-free behavior?
 Is it guaranteed that the Modbus master has consistent access
to the 16 byte sensor data structure?
Modbus connection
N
. For smooth
ENSOR
ET
7 - 1