114 Appendix
Table 45: PROFIsafe F Parameters
F parameters
F_Passivation
F_Block_ID
F_Par_Version
F_Source_Add
F_Dest_Add
F_WD_Time
Manual
Version 1.0.0, valid from HW/SW Version 01/01
Default Value Explanation
The F_Passivation parameter sets the
1
passivation type of the I/O module. The F I/O
module supports channel-granular
Passivation according to RIOforFA. This
value is specified by the WAGO device
description file (GSD/GSDML).
The F_Block_ID parameter specifies the
1
format of the F parameter set. The F I/O
module only supports the value "1."
V2 mode
The F_Par_Version parameter specifies the
PROFIsafe version to be used for
communication. The F I/O module only
supports PROFIsafe Mode V2.
The F_Source_Add parameter specifies the
PROFIsafe source address. To prevent
incorrect parameterization, the address of the
configuration tool is assigned automatically
and cannot be changed. The parameter can
take values from 1 to 65534. The F I/O module
only supports PROFIsafe address type 1 and
does not check the F source address.
The F_Dest_Add parameter specifies the
PROFIsafe destination address of the F I/O
module. For F_Dest_Add, values from 1 to
65534 can be selected. Each address value is
only allowed to appear in the system once.
This is checked by the configuration tool of the
safe PLC. For PROFIsafe communication, the
parameter value must match the PROFIsafe
address of the F I/O module. The F I/O module
only supports PROFIsafe address type 1.
150 ms
The F_WD_Time parameter determines the
monitoring time for PROFIsafe communication
between the safe PLC and F I/O module. At
least one valid PROFIsafe telegram must be
exchanged between the safe PLC and the
F I/O module within the monitoring time. If this
condition is not met, the safe PLC or F I/O
module initiates a safe state. The monitoring
time must be selected in such a way that the
telegram execution times are tolerated, but an
interruption in the connection is still detected
quickly enough. The monitoring time can be
specified in increments of 1 ms. The possible
value range (50 ... 10000 ms) is specified by
the WAGO device description file
(GSD/GDML).
WAGO I/O System
750-662/000-004 8FDI 24V PROFIsafe