WAGO 8FDI 24V PROFIsafe 750-662/000-004 Manual page 86

Table of Contents

Advertisement

86
Diagnostics
Table 37: Diagnostic Messages
Message
Firmware update
required
Inconsistent
F_iPar_CRC
Incorrect
F_CRC_Length
Manual
Version 1.0.0, valid from HW/SW Version 01/01
Diagnostic type Module diagnostic
Coding
0x0231
LED indicator
Module error: red, flashing at 2 Hz
Description/
Checking the firmware image has resulted
remedy
in an inconsistent state. Update the device
firmware.
Note:
Observe the safety advices in Section
"Firmware-Update."
Classification
Error
Diagnostic type Module diagnostic
Coding
0x004B
LED indicator
Module error: red
PROFIsafe status: red
Parameterization status: red, flashing at
1 Hz
Description/
The iPar_CRC of the module is not
remedy
identical to the CRC for the iParameter set
transmitted in the F parameter set.
Generate a consistent combination from
the iParameter set and F parameter set.
Check the iParameter set of the iPar
server if necessary.
Classification
Error
Diagnostic type Module diagnostic
Coding
0x0045
LED indicator
Module error: red
PROFIsafe status: red
Description/
The configured F_CRC length setting is
remedy
not possible in the current operating mode.
Observe the dependency between
F_Par_Version and F_CRC_Length and
select a valid combination.
Classification
Error
WAGO I/O System
750-662/000-004 8FDI 24V PROFIsafe
Description