Commissioning
7.2

Setting the PROFIsafe Address

The PROFIsafe address can be set by the coding switch of the F I/O module or
by the WAGO parameterization tool.
The PROFIsafe address set on the coding switch of the F I/O module has priority
over the PROFIsafe address set by the WAGO parameterization tool.
Only when the address set on the coding switch equals 0 does the setting of the
PROFIsafe address using the WAGO parameterization tool take effect.
Default status address setting
In the default status, the address setting by the coding switch is active.
7.2.1

Setting the PROFIsafe Address using the Coding Switch

Disconnect the power from the node before making the settings!
Switch off the fieldbus node before you pull the F I/O module out of the fieldbus
node to change the settings!
Use only appropriate tools to change the settings!
To set the switching elements of the coding switch, use only suitable objects.
Never exert pressure on the switching elements.
Coding switch is inaccessible when the I/O module is plugged in!
To set the PROFIsafe address on the coding switch, the F I/O module must be
pulled out of the fieldbus node.
Use the switching elements of the coding switch to set the PROFIsafe address to
a value from 1 to 1023.
Manual
Version 1.0.0, valid from HW/SW Version 01/01
WAGO I/O System
750-662/000-004 8FDI 24V PROFIsafe