Setting The Profisafe Address Using The Wago Parameterization Tool; Parameterization Of The F I/O Module With The Wago Parameterization Tool - WAGO 8FDI 24V PROFIsafe 750-662/000-004 Manual

Table of Contents

Advertisement

WAGO I/O System
750-662/000-004 8FDI 24V PROFIsafe
7.2.2
Setting the PROFIsafe Address using the WAGO
Parameterization Tool
To configure the PROFIsafe address through storage in the iParameter set of the
F I/O module, set the PROFIsafe address in the WAGO parameterization tool to
the required value and save the current iParameter set to the F I/O module.
Configuring the F I/O module is described in the section "Parameteriziation of the
F I/O module with the WAGO Parameterization Tool".
7.3
Parameterization of the F I/O Module with the
WAGO Parameterization Tool
Check safety functions!
Before commissioning, all the specified effectiveness of all safety functions must
be verified.
Check the iParameter settings!
After the parameterization of the F I/O module, the parameters read back from
the F I/O module must be compared to the expected values and confirmed. The
new parameters take effect after being confirmed.
Protect against unauthorized modification of the iParameters!
As stated in ISO 13849-1, unauthorized modification of the iParameters must be
prevented. This must be accomplished by secure protection of the F PLC or a
secure application project.
Verify that the parameterization LED is illuminated!
After selecting the F I/O module, check that the F I/O module parameterization
LED is illuminated! A detailed description of indicators is available in section
"Device Description" > "Indicators."
Version 1.0.0, valid from HW/SW Version 01/01
Commissioning
51
Manual

Advertisement

Table of Contents
loading