Diagnostics
Table 37: Diagnostic Messages
Message
Safety shutdown
(internal error)
Short circuit
Undervoltage
field supply
Manual
Version 1.0.0, valid from HW/SW Version 01/01
Diagnostic type Module diagnostic
Coding
0x0219
LED indicator
Module error: red, flashing at 2 Hz
Description/
The F I/O module has entered the safe
remedy
state and switched off the outputs. If the
error occurs repeatedly after restart,
immediately replace the F I/O module and
send it to WAGO for error analysis.
Classification
Error
Diagnostic type Channel diagnostics
Coding
0x0201
LED indicator
Channel status: red
Description/
The input of the F I/O module is not
remedy
powered by the associated clock output or
is connected to a +24 V field supply
directly. Check the input wiring.
Classification
Error
Diagnostic type Module diagnostic
Coding
0x0202
LED indicator
Module error: red
Description/
The 24 V field supply of the F I/O module
remedy
is below the specified tolerance. Correct
the power supply responsible.
Classification
Error