WAGO 8FDI 24V PROFIsafe 750-662/000-004 Manual page 87

Table of Contents

Advertisement

WAGO I/O System
750-662/000-004 8FDI 24V PROFIsafe
Table 37: Diagnostic Messages
Message
Incorrect
F_Par_Version
Internal channel
error
Invalid F_CRC1
Invalid
F_Dest_Add
Invalid
F parameters
Diagnostic type Module diagnostic
Coding
0x0046
LED indicator
Module error: red
PROFIsafe status: red
Description/
The set version of F parameter set is
remedy
incorrect. Observe the dependency
between F_Par_Version and
F_CRC_Length and select a valid
combination.
Classification
Error
Diagnostic type Channel diagnostics
Coding
0x0280
LED indicator
Channel status: red
Description/
The internal hardware test of the F I/O
remedy
module failed. If the error occurs
repeatedly after restart, immediately
replace the F I/O module and send it to
WAGO for error analysis.
Classification
Error
Diagnostic type Module diagnostic
Coding
0x0047
LED indicator
Module error: red
PROFIsafe status: red
Description/
The F_CRC1 formed via the F parameter
remedy
set is invalid. Create a consistent
F parameter set.
Classification
Error
Diagnostic type Module diagnostic
Coding
0x0041
LED indicator
Module error: red
PROFIsafe status: red
Description/
The PROFIsafe address of the F I/O
remedy
module must be in the range of 1 ...
65534. Correct the F parameterization.
Classification
Error
Diagnostic type Module diagnostic
Coding
0x0048
LED indicator
Module error: red
PROFIsafe status: red
Description/
The combination of F parameters is
remedy
invalid. Correct the F parameterization.
Classification
Error
Version 1.0.0, valid from HW/SW Version 01/01