Direct Start From The Configuration Program (Module Level Tci Offline); Adjustable Parameters For Digital Inputs; Table 28: Adjustable Parameters For Digital Inputs - WAGO 8FDI 24V PROFIsafe 750-662/000-004 Manual

Table of Contents

Advertisement

58
Commissioning
(offline). The configuration program passes the current language setting to
WAGO Safety Editor. WAGO Safety Editor starts in OFFLINE mode.
7.3.4.7
Direct Start from the Configuration Program (Module Level TCI
OFFLINE)
In the configuration program of the safe PLC, select an F I/O module and launch
WAGO Safety Editor 75x via the "WAGO Safety-Editor 75x" TCI link. The
configuration program passes the current language setting to WAGO Safety
Editor. WAGO Safety Editor starts in OFFLINE mode.
7.3.5

Adjustable Parameters for Digital Inputs

The following parameters can be adjusted on the digital inputs.

Table 28: Adjustable Parameters for Digital Inputs

Parameter Name
Input Filter Time
Short Circuit Test
Test Pulse Duration
Pre-Evaluation
Discrepancy Time
Restart Inhibit
Operating Mode
*
)
Default setting
Manual
Version 1.0.0, valid from HW/SW Version 01/01
WAGO I/O System
750-662/000-004 8FDI 24V PROFIsafe
Value Range
0 ms (off)
0.2 ms
0.5 ms
1 ms
2 ms
3 ms *
)
5 ms
10 ms
20 ms
50 ms
100 ms
200 ms
Activated *
)
/ Deactivated
0.5 ms
1 ms
2 ms
3 ms
5 ms *
)
10 ms
20 ms
50 ms
100 ms
200 ms
Single-channel *
/ Equivalent / Antivalent
)
5 ... 100 *
)
... 65000 ms
Activated / Deactivated *
Standard *
)
/ Rotary Table
)

Advertisement

Table of Contents
loading

Table of Contents