72
Commissioning
Then configure the F I/O module using the WAGO parameterization tool (see
section "Commissioning" > ... > "Parameterization of the F I/O Module with the
WAGO Parameterization Tool"). The WAGO parameterization tool displays the
iPar_CRC. Make a note of this for the next step (e.g., copy it to clipboard).
Then adjust the PROFIsafe address and the F parameters of the F I/O module by
setting F_iPar_CRC and F_Dest_Add in the hardware configuration environment
to the value from the WAGO parameterization tool or the value of the coding
switch (depending on the setting). See Appendix > "PROFIsafe" > "Overview of
PROFIsafe F Parameters."
Using the default iParameter set
You can use the default iParameter set of the F I/O module without changing the
iParameter settings. Apply the value of the F_iPar_CRC parameter specified in
the Appendix in section "Overview of PROFIsafe F Parameters" by setting
F_iPar_CRC to this value in the hardware configuration environment.
Behavior of the F I/O module when discrepancies occur between
F_iPar_CRC and iPar_CRC
If the F I/O module detects a discrepancy between F_iPar_CRC and iPar_CRC,
safe communication is not established.
If F_iPar_CRC has been set correctly, a match with the iPar_CRC is permanently
stored in the F I/O module.
Next compile the hardware configuration and safety program and check the
assignment of the PROFIsafe subscribers to the respective run-time group. Then
transfer the entire project to the safe PLC.
Observe the required workflows given in the respective manufacturer's
documentation and check and document all safety functions.
Manual
Version 1.0.0, valid from HW/SW Version 01/01
WAGO I/O System
750-662/000-004 8FDI 24V PROFIsafe