WAGO-I/O-SYSTEM 750
750-471 4AI U/I Diff Galv
7
Commissioning
7.1
Parameterization with WAGO-I/O-CHECK
The WAGO-I/O-CHECK software from WAGO Kontakttechnik GmbH & Co. KG
can be used to conveniently and completely configure and parameterize the I/O
module, including:
•
Graphical representation of the bus node
•
Display of the measured values
•
Settings for the application
•
Configuration of the I/O module operating modes
•
Parameterization of module, channel and scaling settings
•
Calibration of channels and adjustment of analog inputs
•
Monitoring
You can obtain the WAGO-I/O-CHECK software on a CD under Item No. 759-
302. This CD contains all the application program files and an explanation. You
can find a description at the internet page at http://www.wago.com!
Save all your settings before you begin parameterization!
To be on the safe side you should always save all of your current settings in a
parameter file before you begin parameterization. This enables you to always
use the original values, should any parameters you are defining not be correct!
Behavior after Overwriting with WAGO-I/O-CHECK !
If WAGO-I/O-CHECK is used to overwrite a parameterization made with the GSD
file, the I/O module operates with the WAGO-I/O-CHECK settings until the 750-
333 and 750-833 Fieldbus Couplers/Controllers are restarted. After restart, the
I/O module is re-parameterized via PROFIBUS using the GSD settings.
All manuals and user guides at all-guides.com
Commissioning
49
Manual
Version 1.0.0