ED34-862
Sticking of Insulator to Indoor Unit Main Body
For safety, be sure to shut off power supply before starting the insulator sticking operation, decoration panel mounting operation, and connecting of connectors for swinging.
Stick the side insulator plate
16
according to the figure below.
16
16
Side insulator plate
Sticking of Absorbent to Panel Horizontal Blade
Perform the operation on soft cloth to prevent damage to the panel.
Perform sticking for the horizontal blades of all air outlets.
Do not apply force to the horizontal blade. (Application of force may lead to horizontal blade
swing failure.)
According to the figure below, stick the horizontal blade absorbent
sealing pad
19
.
(With KDBH55K160, stick the horizontal blade absorbent with matching blade colour.)
Precautions
When the sticking of absorbent and sealant is omitted, condensation may occur.
1
Stick the horizontal blade absorbent
Horizontal blade
Horizontal blade absorbent 17
Front face
A-A cross section
Horizontal blade absorbent 17
17
Sticking reference
Field Setting
Depending on the installation status of the indoor unit's main body, the field setting needs to be performed by remote control operation.
Perform the setting by switching among the following three items: "Mode number", "Setting switch number", and "Setting position number".
The setting procedure and operation method are described in "How to perform field setting" attached to the remote control.
(1) Setting by number of air outlets used
While referring to "How to perform field setting" attached to the remote control, perform the setting according to the table
in the right.
Also, when the corner air outlet is blocked with 4-way blow, set the wind direction slightly downward.
(Note) When the installation height becomes higher than the standard, the setting by ceiling height in (2) becomes
necessary.
(2) Setting by ceiling height
For the ceiling height, refer to the guidelines of ceiling height and number of air outlets used, then perform the setting for
each air outlet used according to the table below.
(Guidelines of ceiling height and number of air outlets used)
Types ~80
Indoor unit
All-around blow
4-way blow
Standard
2.7m or less
3.1m or less
High ceiling 1
3.0m or less
3.4m or less
High ceiling 2
3.5m or less
4.0m or less
FXFQ-P
Precautions
If the sticking of insulator is omitted, condensation may occur.
Sticking reference
For a wiring takeoff point with two sections, make a slit on
the side insulator plate
then route the wiring.
16
Side insulator plate
Side insulator plate
Slit
17
and
18
as well as the horizontal blade
17
in line with the blade shape to the front face of the horizontal blade.
A
A
Horizontal blade
Horizontal blade
Backside
Number of air outlets used
Types 100~
3-way blow
2-way blow
All-around blow
4-way blow
3-way blow
2-way blow
3.0m or less
3.5m or less
3.2m or less
3.4m or less
3.6m or less
4.2m or less
3.3m or less
3.8m or less
3.6m or less
3.9m or less
4.0m or less
4.2m or less
3.5m or less
4.2m or less
4.5m or less
4.2m or less
Values for ceiling height are provided as reference.
Side insulator plate
16
as shown in the figure below,
16
16
Side insulator plate
Wiring
Wiring
Slit
Wiring takeoff point
2
Stick the horizontal blade sealing pad
to the backside of the blade. (For both left and right)
19
19
Sticking reference
19
Sticking reference
Using the base of the rib as a reference, stick without leaving any gap.
Rib
3
Stick the horizontal blade absorbent
18
in between the horizontal blade sealing pad
Horizontal blade absorbent 18
Horizontal blade sealing pad 19
Horizontal blade absorbent 18
[Setting content]
(Setting by number of air outlets used)
(Number of air outlets used)
Mode number
Setting switch number
3-way blow
13 (23)
2-way blow
[Setting content]
(Setting for when corner air outlet is blocked with 4-way blow)
(Wind direction)
Mode number
Standard
13 (23)
Slightly downward
[Setting content]
(Setting by ceiling height)
Mode number
Standard
13 (23)
High ceiling
1
High ceiling
2
: http://splitoff.ru/tehn-doc.html
Accessories
16
Sticking reference
16
16
Sticking reference
16
Side insulator plate
16
Side insulator plate
Superimpose the surplus section.
Horizontal blade sealing pad 19
19
.
18
Sticking reference
18
Sticking reference
B
B
B-B cross section
Setting position number
02
1
03
Setting position number
02
4
03
Setting position number
01
0
02
03
J : 1P191031A
2
93

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents