Daikin VRV III Manual page 93

Hide thumbs Also See for VRV III:
Table of Contents

Advertisement

Accessories
[ PRECAUTIONS ]
• Inproper screwing of the screws may cause the
troubles shown in Fig. 7 Screw properly.
• If gap is still left between the ceiling and the decoration panel after screwing the screws, readjust the indoor
unit body height. (Refer to Fig. 8)
No gap is allowed
(3) Wiring of the decoration panel (Refer to Fig. 9)
6 Remove the electric components box lid.
7 Connect the connectors for swing flap motor lead wire installed on the decoration panel.
8 Replace the electric components box lid reversing the procedure to remove it.
Make sure that the swing flap motor lead wire is not caught between the electric components box and its lid,
and between the indoor unit body and the decoration panel.
88
Air leak from ceiling
Contamination
Adjustment of the indoor unit body
height from the holes in the corner
of the decoration panel is possible
if the indoor unit is kept leveled and
the drain piping, etc. is unaffected.
Fig. 8
: http://splitoff.ru/tehn-doc.html
Air leak
Dew formation, dew dripping
Fig. 7
ED34-862
FXFQ-P