Installation
(When drain hose is connected)
NOTE
• To ensure no excessive pressure is applied to the included drain hose (1), do not bend or twist when installing.
(This may cause leakage.)
• If converging multiple drain pipes, install according to the procedure shown below.
Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
(2) Confirm that smooth drainage is achieved after the piping work.
• Add 0.6 liter of water in the drain pan from the air outlet for confirming drainage. (Refer to Fig. 25)
CAUTION
• Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage
might enter the indoor unit through the drain pipes and corrode the heat exchanger.
• Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.
328
Good
Tilt down
Fig. 21
Metal clamp (2) (accessory)
Taping area
Fig. 22
Sealing pad (8) (accessory)
Metal clamp (2)
(accessory)
< Facing rear right or right >
Fig. 23
T-joint converging drain pipes
Slope downwards at a gradient of at least 1/100
Portable pump
Bucket
Fig. 25
Do not lift
Wrong
Make sure it is
not in the water
Drain hose (1)
(accessory)
Metal clamp
(2)
(accessory)
Sealing pad (8)
(accessory)
(length : mm)
< Facing rear left or left >
Wrong
Fig. 24
Air outlet
: http://splitoff.ru/tehn-doc.html
ED34-862
Make sure there
is no slack
C : 3PN01417-7P