Installation Manual
CAUTION
• The indoor and outdoor units and the power supply wiring and remote controller cord must be installed
at least 1m away from any televisions or radios. This is to prevent interference with picture and sound
reception. (Interference may occur even at 1m away depending on the reception quality.)
• If installing the wireless kit, the distance of the signal sent from the remote controller might be shorter if
there are fluorescent lights which are electrically started (such as with inverters, rapid starters, etc.) in
the room. The indoor unit should be installed as far away from fluorescent lights as possible.
(2) Ceiling height
This product can be installed in ceilings up to 3.5m high (4.2m high for the 100 and 125).
If the ceiling height is 2.7m (3.2m for the 100 and 125) or more, field settings will have to be made with the
remote controller. See "11. FIELD SETTING" for details.
(3) Air direction
The air direction shown in Fig. 3 is an example.
Select the appropriate number of directions according to the shape of the room and the location of the unit.
(Field settings have to be made using the remote controller and the outlet vents have to be shut off if two,
three, or four (corner shut-off) directions are selected. See the shut-off materials (sold separately) instal-
lation manual for details.)
(4) Use eyebolts for installation. Check if the location for the installation is strong enough to support the weight
of the unit, reinforce it if necessary, and install using eyebolts. (The spacing of the installation is shown on
the "paper pattern for installation (5)".)
English
66
[Air direction]
All-round air
Four air direction
Fig. 3
Three air direction
Two air direction
: http://splitoff.ru/tehn-doc.html