Daikin VRV III Manual page 145

Hide thumbs Also See for VRV III:
Table of Contents

Advertisement

Accessories
Filter Chamber
Specifications
Item
External
Dimensions (mm)
Applicable Models
Precaution at use
1. The filter chamber will be needed when the high efficiency filter will be built in. But, it is impossible to build in more
than two kinds filter at the same time.
Installation
High Efficiency Filter (Filter chamber is required for the high efficiency filter)
Specifications
Model
Item
External Dimensions
(30×460×145)
(H×W×D)(mm)
×2
Dust Collection
65% (Colorimetric method)
Efficiency (%)
Initial Pressure Loss
29
(Pa)
Final Pressure Loss
78
(Pa)
Filter
Non-woven fabric of synthetic fiber
Life Time (h) ∗
2500 hours
20 · 25 · 32
Applicable Models
Note:
1. ∗ The life time at the dust density 0.15 mg/m³.
2. Replace the fan motor's capacitor in accordance with the guide in next page, when the high efficiency filter is
used.
140
Model
KDDFJ53G36
H
50
W
780
D
600
20 · 25 · 32 Class
KAFJ532G36
KAFJ532G56
KAFJ532G80
(30×675×145)
(30×860×145)
×2
×2
40 · 50
63
Class
Class
Class
KDDFJ53G56
KDDFJ53G80
50
50
995
1180
600
600
40 · 50 Class
63 Class
KAFJ532G160
KAFJ533G36
(30×660×145)
(30×460×145)
×4
×2
90% (Colorimetric method)
39
39
78
Non-woven fabric of synthetic fiber
2500 hours
80 · 125
20 · 25 · 32
Class
Class
: http://splitoff.ru/tehn-doc.html
ED34-862
KDDFJ53G160
50
1670
600
80 · 125 Class
KAFJ533G56
KAFJ533G80
KAFJ533G160
(30×675×145)
(30×860×145)
(30×660×145)
×2
×2
×4
49
2100 hours
2000 hours
40 · 50
63
80 · 125
Class
Class
Class
FXCQ-M

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents