Daikin VRV III Manual page 104

Hide thumbs Also See for VRV III:
Table of Contents

Advertisement

ED34-862
Figure 4
Mounting status
Suction chamber
Hook
Match the contour
Suspension bracket
Indoor unit main body
Installation of Indoor Unit Main Body and Suction Chamber
• Install the indoor unit main body and suction chamber.
At the time of installation, perform the engineering work according to the installation
manual attached to the indoor unit main body. (For the installation height, refer to the figure
to the right.)
• When mounting the suction chamber to the existing indoor unit main body, change the
installation height of the indoor unit main body to height
Mounting of Connecting Chamber and Connection of Flexible Duct
Mount the connecting chamber. (1 piece each for left and right, a total of 2 pieces)
(1) Press the square hole area of the connecting chamber
section (tab) of the suction chamber
(2) Using the supplied screws
, fix the connecting chamber. (2 positions)
6
Connecting chamber left (right)
2
(
3
)
Screw
6
Outside air inlet
1
Suction chamber
Figure 7
Mounting of connecting chamber
(This figure shows the connecting chamber (left)
In case of KDDP55K160K
(3) Connect the connecting chamber and T joint.
Flexible duct
Connecting chamber (right)
3
2
Connecting chamber (left)
Insert the flexible duct
until the base of the
Figure 8
connecting chamber.
<<Duct: Nominal diameter φ150>>
Duct Connection
(1) Connect the duct to the duct connection area.
(2) Wrap the connection area with vinyl tape, etc., (arrangement at site) to prevent an air leak.
Precautions
For the duct, be sure to apply the insulation treatment to prevent condensation.
Do not perform duct manipulations described in the figure to the right.
Beware that, in accordance with the local law, there may be cases where the use of a nonflammable duct is
compulsory.
When a duct goes through fire protection areas including a fire proof structure, beware that, in accordance with the local law, it may be required to establish a damper or to build a
structure that is not detrimental to fire protection.
When penetrating a wooden construction wall with a metal duct, apply electrical insulation to the duct and wall.
Mount the outside duct so that it has a downslope toward the outside, and prevent rainwater from leaking in with a hood, etc. (Gradient of 1/100 to 1/50)
To prevent the intrusion of small animals, such as birds, and bugs, be sure to attach a netting to sections open to outside air.
To protect the heat exchanger of the indoor unit, be sure to attach an air filter to sections open to outside air.
Mounting of Decoration Panel
• After temporarily hooking the decoration panel, pass the swing motor lead wire, which is coming out from the decoration panel, through the wiring hole of the suction chamber.
However, when used in combination with the air purifier unit or streamer deodorization unit, perform wiring without routing through the wiring hole.
• Mount the decoration panel according to the installation manual attached to the decoration panel.
With an air purifier unit or
streamer deodorization unit
FXFQ-P
1
Fixing method of hook
in the figure to the right.
Figure 7
(
) into the hook
2
3
. (2 positions)
1
Square hole
(Procedure 1)
Press the square hole area of the
connecting chamber
(
) into the
2
3
hook section of suction chamber
1
.
(2 positions each)
(Procedure 2)
Using the supplied screws
6
, fix the
connecting chamber. (2 positions each)
.)
2
Drawing of mounting
at completion
Figure 8
11
10
T joint
Hanging band for duct
Duct (field supplied)
(field supplied)
(φ150)
12
Sealing pad
To prevent applying weight to the
connecting chamber, hang the T
joint using the hanging band for
the duct.
Suction chamber
1
Wiring hole
Swing motor lead wire: Route from the panel side to the
1
suction chamber
.
(After temporarily hooking the decoration panel, pass
through the wiring hole.)
Decoration panel
Figure 5
Status after mounting
Hook
Hook
Suspension bracket
Suspension bracket
Indoor unit
main body
Suction chamber
<How to Tight Sealing Pad>
(1)
(2)
7
Flexible duct
(1) Wrap the sealing pad
(2) Insert the tip of the
to the position to be
band through the
tightened.
gap of the split pin,
then lightly tighten
by hand.
Precautions
Because the split pin has a structure to prevent counter rotation, be careful with the
turning direction. (When a counter rotation is forced, the ratchet will be damaged, and
the tightening force will be weakened.)
(4) Mount the supplied installation pattern paper to the indoor unit by using screws to
cure the indoor unit.
(Refer to the installation manual of the indoor unit main body.)
(Refer to the figure below.)
(Mounting of installation
pattern paper)
• Complete all the refrigerant and drain piping works for the indoor unit main body.
a) Extreme bending
With wireless unit
• For details on connection method, refer to the installation manual
attached to the wireless remote control kit (sold separately).
: http://splitoff.ru/tehn-doc.html
Accessories
Figure 6
Drawing of mounting at completion
1
Suction chamber
Indoor unit main body
(mm)
Suspension bracket
BYCP125K-W1
180
Ceiling surface
(3)
(4)
Split pin
correct
wrong
(3) Using a standard
(4) This completes
tool (driver, pliers,
the mounting.
etc.), turn the split
pin to the direction
shown in the figure
to tighten the band.
Installation pattern paper
(Supplied with the indoor unit
main body)
Screw
(Supplied with the indoor unit
main body)
b) Multiple bending
c) Reduction of connecting duct diameter
JC : 3K017588C
2
99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents