ED34-862
Installation
Installation of the filter frame
Attach the filter frame to the indoor unit, where the original filter was located. (Refer to the operation manual of the
indoor unit how to remove the standard filter. The standard filter removed shall not be used.)
1. Loose the screw of the metal bracket located on each end of the filter frame and hook the filter frame temporarily
to the partition plate located at the center of the indoor unit.
2. Fasten the screw of the metal bracket tightly.
Replacement guide of capacitor for fan motor
FXCQ-M
In case of KAFJ532G160 and KAFJ533G160
There are four filter frames of 2 kinds of each
having different position of the metal bracket.
Install the filter frames to the indoor unit as
shown below.
Capacity of a capacitor to be replaced.
Model
Capacitor's Capacity
2 µ F
KAFJ532 · 533G36
2 µ F
KAFJ532 · 533G56
2 µ F
KAFJ532 · 533G80
4.5 µ F
KAFJ532 · 533G160
6 µ F
: http://splitoff.ru/tehn-doc.html
Accessories
3
Applicable Models
20 · 25 · 32 Class
40 · 50 Class
63 Class
80 Class
125 Class
141