Specifications
Floor Standing Type
Model
1 Cooling Capacity (19.5°CWB)
2 Cooling Capacity (19.0°CWB)
Casing Color
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
4 Sound Level (H/L) (220V)
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.
Note:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
5 Refer to page 373 for Fan Motor Input.
362
FXLQ40MAVE
kcal/h
4,000
Btu/h
16,000
kW
4.7
kW
4.5
Ivory White (5Y7.5/1)
mm
600×1,140×222
mm
3×14×1.5
0.200
2D14B13
Sirocco Fan
W
25×1
m³/min
11/8.5
cfm
388/300
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
φ
mm
6.4 (Flare Connection)
φ
mm
12.7 (Flare Connection)
φ
mm
21 O.D (Vinyl Chloride)
kg
30
dBA
38/33
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A PA Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.
FXLQ50MAVE
5,000
19,800
5.8
5.6
Ivory White (5Y7.5/1)
600×1,420×222
3×14×1.5
0.282
2D14B20
Sirocco Fan
35×1
14/11
494/388
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
φ
6.4 (Flare Connection)
φ
12.7 (Flare Connection)
φ
21 O.D (Vinyl Chloride)
36
39/34
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A PA Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.
C : 3D038816A
: http://splitoff.ru/tehn-doc.html
ED34-862
FXLQ63MAVE
6,300
24,900
7.3
7.1
Ivory White (5Y7.5/1)
600×1,420×222
3×14×1.5
0.282
2D14B20
Sirocco Fan
35×1
16/12
565/424
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
φ
9.5 (Flare Connection)
φ
15.9 (Flare Connection)
φ
21 O.D (Vinyl Chloride)
36
40/35
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A PA Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
FXLQ-MA / FXNQ-MA