Installation Manual
3. OPTIONAL ACCESSORIES
• The optional decoration panel and remote controller are required for this indoor unit. (Refer to Table 1, 2)
(However, the remote controller is not required for the slave unit of a simultaneous operation system.)
Table 1
FXFQ25 · 32 · 40 · 50 · 63 · 80 · 100 · 125PVE
• These are two types of remote controllers: wired and wireless. Select a remote controller from Table 2
according to customer request and install in an appropriate place.
Table 2
Wired type
Wireless type (Heat pump type/Cooling only type)
NOTE
• If you wish to use a remote controller that is not listed in "Table 2" on page 4, select a suitable remote con-
troller after consulting catalogs and technical materials.
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND
CHECK AFTER INSTALLATION IS FINISHED.
1. Items to be checked after completion of work
Items to be checked
Are the indoor unit and outdoor unit fixed
firmly?
Is the outdoor unit fully installed?
Is the gas leak test finished?
Is the unit fully insulated?
Does drainage flow smoothly?
Does the power supply voltage correspond
to that shown on the name plate?
Are wiring and piping correct?
Is the unit safely grounded?
Is wiring size according to specifications?
Is something blocking the air outlet or inlet
of either the indoor or outdoor units?
Are refrigerant piping length and additional
refrigerant charge noted down?
2. Items to be checked at time of delivery
* Also review the "1. SAFETY PRECAUTIONS"
Items to be checked
Are the terminal box lid, air filter, suction grille attached?
Did you explain about operations while showing the instruction manual to your customer?
Did you hand the instruction manual over to your customer?
English
64
Unit model
Remote controller
If not properly done, what is likely to occur
The unit may drop, vibrate or make noise.
The unit may malfunction or the compo-
nents burn out.
It may result in insufficient cooling.
Condensate water may drip.
Condensate water may drip.
The unit may malfunction or the compo-
nents burn out.
The unit may malfunction or the compo-
nents burn out.
It may result in electric shock.
The unit may malfunction or the compo-
nents burn out.
It may result in insufficient cooling.
The refrigerant charge in the system is not
clear.
Optional decoration panel
BYCP125K-W1
Color : Fresh white
BRC1C62
BRC7F634F/BRC7F635F
: http://splitoff.ru/tehn-doc.html
ED34-862
Check
Check
4
3P161684-3B
FXFQ-P