Daikin VRV III Manual page 110

Hide thumbs Also See for VRV III:
Table of Contents

Advertisement

ED34-862
Installation of Indoor Unit Main Body and High Efficiency Filter Unit
• Install the indoor unit main body and high efficiency filter unit.
At the time of installation, perform engineering work according to the installation manual attached
to the air conditioner's main body. (For the installation height, refer to the figure to the right.)
• When mounting the high efficiency filter unit to the existing indoor unit main body, change the
installation height of the indoor unit main body to height
• Mount the supplied installation pattern paper to the indoor unit using screws to
cure the indoor unit.
(Refer to the installation manual for the indoor unit main body.)
(Refer to the figure below.)
[Mounting of installation pattern paper]
• Complete all the refrigerant and drain piping work for the indoor unit main body.
Mounting of Decoration Panel and Mounting of High Efficiency Filter
• After temporarily hooking the decoration panel, pass the swing motor lead wire, which is coming out from the decoration panel, through the wire through hole of
the high efficiency filter unit.
• Mount the decoration panel according to the installation manual attached to the decoration panel.
• Mounting of high efficiency filter
After the completion of wiring and sticking of sealing pad (2 positions), mount the high efficiency
filter.
Figure 6
Figure 7
With wireless unit
• Route the connector of the receiver lead wire through the wire through hole, then connect the connector on the indoor PC board ass'y.
• For details on the connection method, refer to the installation manual attached to the wireless remote control kit (sold separately).
Preparation of Indoor Unit
• With the mounting of a high efficiency filter unit, setting the indoor unit main
body is required.
Using the field setting mode on the remote control, switch to the setting
position number as shown in the table to the right.
For the field setting mode, refer to "How to perform field setting" attached to
the remote control.
FXFQ-P
in the figure to the right.
Installation pattern paper
(Supplied with indoor unit main body)
M4×12 Screws
(Supplied with indoor unit main body)
High efficiency
filter chamber
Wire through hole
Swing motor lead wire:
Route from the panel side to
the high efficiency filter chamber.
(After temporarily hooking
the decoration panel,
pass through the wire through hole.)
Decoration panel
Mode number
13 or 23
: http://splitoff.ru/tehn-doc.html
Indoor unit
main body
High efficiency filter unit
(mm)
BYCP125K-W1
180
Sealing pad (supplied): For preventing air bypass
Figure 6
(Stick to 2 positions in the same manner.)
Decoration panel
High efficiency
filter unit
Rotate the filter clasp by 90˚ to
fix the filter.
(4 positions)
Filter clasp
High efficiency filter
Figure 7
Setting switch number
Setting position number
0
02
1
02
Accessories
2
Suspension bracket
(Installation height
guideline)
Ceiling surface
Remarks
80 only
Both 80 and 160
JC : 3K015220E
105