ED34-862
FXMQ100PVE
(mmH
O) (Pa)
2
250
25
200
20
150
15
100
10
50
5
0
0
20
22
(mmH
O)
(Pa)
2
FXMQ125PVE
(mmH
O) (Pa)
2
250
25
Upper limit of ESP
(NOTE 8)
200
20
150
15
100
10
50
5
0
0
23
25 27 29
(mmH
O)
2
FXMQ-P
(mmH
Upper limit of ESP
(NOTE 8)
Upper limit
of ESP by
airflow auto
adjustment
"HH"
Lower limit
"H"
of ESP by
airflow auto
"L"
adjustment
24
26
28
30
32
34
36
37
Air flow (m
3
/min)
(mmH
(mmH
Upper limit
of ESP by
airflow auto
adjustment
"HH"
"H"
Lower limit
"L"
of ESP by
airflow auto
adjustment
31
33
35
37 39
41
43
Air flow (m
3
/min)
(mmH
Notes:
O)
2
1. As for this machine, less than 10% of the volume of
25
blow-off air is automatically adjusted to the rated
quantity by airflow auto adjustment at the time of
installation.
2. After duct construction completion, please perform
local setting "airflow auto adjustment" by remote
controller.
20
3. About the local setting method of the "airflow auto
adjustment", look at the installation manual which is
attached to an indoor unit.
4. External static pressure that can adjust by "airflow
auto adjustment" function is 50Pa - 200Pa (When
air flow is HH).
15
5. It is not operated auto adjustment, operated in air
flow that is different from rated quantity in the case
of use out of external static pressure range
mentioned above.
6. This figure shows a fan characteristics at the time of
"HH" "H" and "L".
10
7. The remote controller can be used to change "HH"
"H" and "L".
8. ESP : external static pressure.
9. Please set the external static pressure of the
suction duct at 150Pa or less.
5
0
O)
2
Notes:
O)
2
1. As for this machine, less than 10% of the volume of
25
blow-off air is automatically adjusted to the rated
quantity by airflow auto adjustment at the time of
installation.
2. After duct construction completion, please perform
local setting "airflow auto adjustment" by remote
controller.
20
3. About the local setting method of the "airflow auto
adjustment", look at the installation manual which is
attached to an indoor unit.
4. External static pressure that can adjust by "airflow
auto adjustment" function is 50Pa - 200Pa (When
air flow is HH).
15
5. It is not operated auto adjustment, operated in air
flow that is different from rated quantity in the case
of use out of external static pressure range
mentioned above.
6. This figure shows a fan characteristics at the time
10
of "HH" "H" and "L".
7. The remote controller can be used to change "HH"
"H" and "L".
8. ESP : external static pressure.
9. Please set the external static pressure of the
suction duct at 150Pa or less.
5
0
O)
2
: http://splitoff.ru/tehn-doc.html
Fan Performances
7
3D060581A
3D060582A
265