Daikin VRV III Manual page 200

Hide thumbs Also See for VRV III:
Table of Contents

Advertisement

ED34-862
[ PRECAUTIONS ]
• Refer to the "REMOTE CONTROLLER INSTALLATION
MANUAL" on how to install and lay the wiring for the remote
controller.
• See also the "Wiring Diagram plate" attached to the control
box lid when laying electrical wiring.
• Connect the remote controller and transmission wiring their
respective terminal blocks.
CAUTION
• Do not, under any circumstances, connect the power sup-
ply wiring to the remote controller or transmission wiring
terminal block. Doing so can destroy the entire system.
[ Connecting electrical wiring, remote controller wiring,
and transmission wiring ] (Refer to Fig. 18)
Indoor PCboard (ASSY)
P 1 P 2 F 1 F 2 T 1 T 2
R E M O T E
T R A N S M I S S I O N
F O R C E D
C O N T R L
W I R I N G
O F F
Terminal block (6P)
Remote controller wiring
Transmission wiring
P
P
1
2
REMOTE
CONTRL
Fig. 18
• Power supply and Earth wiring
Remove the control box lid.
Next, pull the wires into the unit through the wiring through
hole and connect to the terminal block (3P).
Be sure to put the part of the sheathed vinyl into the control
box.
• Remote controller and transmission wiring
Pull the wires into the unit through the wiring through hole
and connect to the terminal block (6P).
Be sure to put the part of the sheathed vinyl into the control
box.
<Precautions when laying power supply wiring >
• Wiring of different thicknesses cannot be connected to the
power supply wiring terminal block. (Slack in the power sup-
ply wiring may cause abnormal heat.)
English
FXDQ-PB / FXDQ-NB
Terminal block (3P)
Power supply wiring
Earth wire
Wiring through hole
L
N
Wiring through hole
F
F
T
T
1
2
1
2
TRANSMISSION
FORCED
WIRING
OFF
• Use sleeve-insulated round crimp-style terminals for connec-
tions to the power supply wiring terminal block. When none
are available, connect wires of the same diameter to both
sides, as shown in the figure.
Insulation sleeve
Round crimp-style terminal
Connect wires of
Do not connect
the same gauge to
wires of the same
both sides.
gauge to one side.
Follow the instructions are below if the wiring may get very
hot due to slack in the power supply wiring.
• For wiring, use the designated power supply wiring and con-
nect firmly, then secure to prevent outside pressure being
exerted on the terminal board.
• Use the correct screwdriver for tightening the terminal
screws. If the blade of screwdriver is too small, the head of
the screw might be damaged, and the screw will not be prop-
erly tightened.
• If the terminal screws are tightened too hard, screws might
be damaged.
• Refer to the table below for the tightening torque of the termi-
nal screws.
Terminal block
Remote controller / transmission wiring
terminal block (6P)
Power supply wiring terminal block (3P)
[ WIRING EXAMPLE ]
No. 1 system When using 1 remote controller for
1 indoor unit
Power supply
Power supply
single phase
single phase
Outdoor unit
50Hz 220-240V
50Hz 220-240V
L N
L N
IN/D
OUT/D
F
F
F
F
1
1
2
2
L
N
P
P
F
F
T
T
L
N
P
1
2
1
2
1
2
Indoor unit A
Indoor unit B
P
P
1
2
Remote controller
Remote controller
(option)
Fig. 19
: http://splitoff.ru/tehn-doc.html
Installation
Electric wire
Do not connect
wires of different
gauges.
Tightening torque (N·m)
0.79 – 0.97
1.18 – 1.44
Power supply
single phase
50Hz 220-240V
L N
P
F
F
T T
L
N
P
P
F
F
T
T
1
2
1
2
1
2
1
2
1
2
1
2
Most
downstream
Indoor unit
P
P
P
P
1
2
1
2
Remote controller
(option)
(option)
11
3PN09042-1A
195
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents