Daikin VRV III Manual page 339

Hide thumbs Also See for VRV III:
Table of Contents

Advertisement

Specifications
Wall Mounted Type
Model
1 Cooling Capacity (19.5°CWB)
2 Cooling Capacity (19.0°CWB)
Casing Color
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
4 Sound Level (H/L) (220-240V)
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.
Note:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp : 35°CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp : 35°CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
5 Refer to page 340 for Fan Motor Input.
334
FXAQ40MAVE
kcal/h
4,000
Btu/h
16,000
kW
4.7
kW
4.5
White (3.0Y8.5/0.5)
mm
290×1,050×230
mm
2×14×1.4
0.213
QCL9686M
Cross Flow Fan
W
43×1
m³/min
12/9
cfm
424/318
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ
mm
6.4 (Flare Connection)
φ
mm
12.7 (Flare Connection)
VP13
mm
(External Dia. 18 Internal Dia. 13)
kg
14
dBA
39/34
Fuse
Electronic Expansion Valve
R-410A PA Series
Operation Manual. Installation
Manual. Installation Panel. Paper
Pattern for Installation. Insulation
Tape. Clamps. Screws.
FXAQ50MAVE
5,000
19,800
5.8
5.6
White (3.0Y8.5/0.5)
290×1,050×230
2×14×1.4
0.213
QCL9686M
Cross Flow Fan
43×1
15/12
530/424
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ
6.4 (Flare Connection)
φ
12.7 (Flare Connection)
VP13
(External Dia. 18 Internal Dia. 13)
14
42/36
Fuse
Electronic Expansion Valve
R-410A PA Series
Operation Manual. Installation
Manual. Installation Panel. Paper
Pattern for Installation. Insulation
Tape. Clamps. Screws.
C : 3D039370B
: http://splitoff.ru/tehn-doc.html
ED34-862
FXAQ63MAVE
6,300
24,900
7.3
7.1
White (3.0Y8.5/0.5)
290×1,050×230
2×14×1.4
0.213
QCL9686M
Cross Flow Fan
43×1
19/14
671/494
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ
9.5 (Flare Connection)
φ
15.9 (Flare Connection)
VP13
(External Dia. 18 Internal Dia. 13)
14
46/39
Fuse
Electronic Expansion Valve
R-410A PA Series
Operation Manual. Installation
Manual. Installation Panel. Paper
Pattern for Installation. Insulation
Tape. Clamps. Screws.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
FXAQ-MA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents