Accessories
Natural Evaporating Pan Type Humidifier (Wiring adaptor is required.)
Specifications
Model
Item
Humidifying Capacity (L/h)
Power Supply (W)
Power Consumption
Water Inlet Port
Water Outlet Port
Applicable Models
Precaution at use
1. "Wiring adaptor (KRP1B61)" is separately needed for one indoor unit by one piece of the adaptor.
2. This humidifier will be built in a indoor unit, while the solenoid valve box will be mounted out of the unit's body
(refer to the dimensions of optional accessories).
3. The field setting should be changed by a remote controller.
Note:
The value in JIS heating condition's standard.
Feed water piping
1. Provide a stop valve of feed water for the feed water circuit.
2. Supply clean water for the feed water. Contaminated water clogs a valve and the contaminants accumulate in a
water tank, disturbing a normal operation of the humidifier. (Never use cooling water for a cooling tower or hot
water for heating purpose). Moreover, since white powder will appear if the feed water contains much silica, it is
recommended to install a water purifier or a water softener if these phenomena are found.
3. Use water in the range of water temperature 5 ~ 50°C and water pressure 0.049 ~ 0.294 MPa[0.5 ~3kg/cm²].
Provide a reducing valve between a strainer and this kit, in case of 0.294MPa or more for feed water pressure.
4. The feed water pipe can not be connected to a public water route. Accordingly, if water must be supplied through
a public water by all means, provide a cistern tank (approved model only).
Wiring diagram
------------- Field wiring
Make wiring as shown on the
right, if a humidity controller
will be mounted.
Arrange the wiring shown
right locally for that case. Set
the turn-over switch to OFF
for the choice of ON/OFF of
group humidity controlling
input on the "Wiring adaptor
PC board" .
Characteristics of Filter
230
KNM25K32V1
KNM25K50V1
0.4
0.6
Single Phase, 220-240V 50Hz
VP25 (External dia. φ 32) (drain pipe at indoor unit)
20 · 25 · 32 Class
40 · 50 Class
KNM25K63V1
1.0
12/9.6
1/2B
63 Class
: http://splitoff.ru/tehn-doc.html
ED34-862
KNM25K125V1
1.8
80 · 100 · 125 Class
FXSQ-M