The operation is available when the outdoor air temperature is down to -15°C
(Operation when the outdoor air temperature becomes lower than -10°C)
When the outdoor air suction temperature becomes lower than -10°C, the unit is changed to intermittent operation to
prevent freezing of the heat exchanger element and dew condensation within the unit.
Intermittent operation
The outdoor air thermistor (standard equipment) within the unit detects the temperature. According to the detected
temperature, the following operation determines.
<Step 1>
The air supply fan is changed to intermittent operation, when the temperature is lower than -10°C.
The intermittent operation of the air supply fan is changed to an operation of each cycle for 45 minutes' operation
after stopping operation for 15 minutes.
The exhaust fan operates continuously according to setup.
<Step 2>
When the temperature becomes lower than -15°C, the unit stops operation to prevent any defect, such as dew
condensation and freezing. The unit does not ventilate.
But, to detect the elevation of the outdoor air temperature, the unit operates for 5 minutes per hour.
The control by the external damper (local purchase) is available.
When the unit is not operating, the unit prevents the cool outdoor air from invading.
The power is applied from the connector X15A to the external damper. Therefore, the operation of the unit is
controlled in conjunction with the external damper.
Note:
Local setting is required.
The high efficiency filter (that has 65% of average dust collecting efficiency) is suitable
High efficiency filter
Air filter
Additional optional accessories
Built-in optional high efficiency filter
BRP4A50: Heater control kit
General Information
Maintenance cover
Control box
Install the high efficiency
filter to meet the direction
of the arrow of the name plate.
Heat exchanger element
High efficiency filter
AIR
FLOW
The side of heat
exchanger element
Rail
Rail
Install the high efficiency filter
along the inside of the rail.