Daikin VRV III Manual page 193

Hide thumbs Also See for VRV III:
Table of Contents

Advertisement

Installation
4.
PREPARATIONS BEFORE INSTALLATION
(1) Confirm the positional relationship between the unit
and suspension bolts. (Refer to Fig. 2)
• Install the inspection opening on the control box side where
maintenance and inspection of the control box and drain
pump are easy. Install the inspection opening also in the
lower part of the unit.
620
500
Suspension
bolt pitch
Air outlet
Drain pump
Model
20 · 25 · 32 type
40 · 50 type
63 type
(2) Make sure the range of the unit's external static pres-
sure is not exceeded.
(See the technical documentation for the range of the
external static pressure setting.)
4
188
(length : mm)
Air inlet
Control box
450×450
(Inspection
opening size)
Ceiling
〈SERVICE SPACE〉
620
Allow view
Inspection door
Fig. 2
(Ceiling opening)
(length: mm)
A
B
700
740
900
940
1100
1140
(3) Open the installation hole. (Pre-set ceilings)
• Once the installation hole is opened in the ceiling where
the unit is to be installed, pass refrigerant piping, drain
piping, transmission wiring, and remote controller wiring
(It is not necessary if using a wireless remote controller)
to the unit's piping and wiring holes.
See "6. REFRIGERANT PIPING WORK", "7. DRAIN
PIPING WORK", and "10. WIRING EXAMPLE".
• After opening the ceiling hole, make sure ceiling is level if
needed. It might be necessary to reinforce the ceiling
frame to prevent shaking.
Consult an architect or carpenter for details.
(4) Install the suspension bolts.
(Use W3/8 to M10 suspension bolts.)
Use a hole-in-anchor for existing ceilings, and a sunken
insert, sunken anchor or other part to be procured in the
field to reinforce the ceiling to bearing the weight of the unit
for new ceiling. (Refer to Fig. 3)
Indoor unit
Note: All the above parts are field supplied.
Fig. 3
(5) For bottom intake, replace the chamber lid and protec-
tion net in the procedure listed in Fig. 4.
(1) Remove the protection net.
(6 locations)···PBVE(T) type only
Remove the chamber lid. (7 locations)
(2) Reattached the removed chamber lid in the orientation
shown in Fig. 4. (7 locations)
Reattached the removed protection net in the orienta-
tion shown in Fig. 4.
(6 locations)···PBVE(T) type only
(3) Attach the air filter (accessory) in the manner shown in
the diagram.
The four holes which cannot be covered by the air filter
should be covered with commercially available tape.
(1)
Air discharge
(2)
Air discharge
Fig. 4
: http://splitoff.ru/tehn-doc.html
ED34-862
Ceiling slab
Anchor bolt
Long nut or turn-buckle
Suspension bolt
Protection net
Air inlet
Chamber lid
Chamber lid
Protection net
Air inlet
English
3PN09042-1A