ED34-862
Ceiling Mounted Duct Type
Model
∗
1 Cooling Capacity (19.5°CWB)
∗
2 Cooling Capacity (19.0°CWB)
Casing
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number
of Units
Fan
Air Flow Rate (HH/H/L)
External Static
Pressure
Drive
Temperature Control
Air Filter
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Mass (Weight)
∗
6 Sound Level (HH/H/L) dBA
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.
Note:
∗
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
∗
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
∗
3 External static pressure is changeable in 13 or 14 stages within the ( ) range by remote controller.
∗
4 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric method (gravity method)
50% or more.
5 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
∗
6 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
7 Refer to page 255 for Fan Motor Input.
FXMQ-P
FXMQ100PVE
kcal/h
10,000
Btu/h
39,600
kW
11.6
kW
11.2
Galvanized Steel Plate
mm
300×1,400×700
mm
3×16×1.75
m²
0.383
—
Sirocco Fan
W
350×1
m³/min
32/27/23
cfm
1,130/953/812
Pa
Standard 100 (200-50
Direct Drive
Microprocessor Thermostat for Cooling and Heating
∗
4
φ
mm
9.5 (Flare Connection)
φ
mm
15.9 (Flare Connection)
VP25
mm
External Dia. 32
(
Internal Dia. 25
kg
46
220V
43/41/39
240V
43/41/39
Fuse.
Fan Driver Overload Protector.
Electronic Expansion Valve
R-410A PA Series
Operation Manual. Installation Manual. Drain Hose. Clamp
Metal. Insulation for Fitting. Sealing Pads. Clamps.
Washers. Screws. Air Discharge Flange. Air Suction
Flange.
∗
3)
Microprocessor Thermostat for Cooling and Heating
)
Fan Driver Overload Protector.
Operation Manual. Installation Manual. Drain Hose. Clamp
Metal. Insulation for Fitting. Sealing Pads. Clamps.
Washers. Screws. Air Discharge Flange. Air Suction
Flange.
C : 3D060388A
: http://splitoff.ru/tehn-doc.html
Specifications
FXMQ125PVE
12,500
49,500
14.5
14.0
Galvanized Steel Plate
300×1,400×700
3×16×1.75
0.383
—
Sirocco Fan
350×1
39/33/28
1,377/1,165/988
∗
Standard 100 (200-50
3)
Direct Drive
∗
4
φ
9.5 (Flare Connection)
φ
15.9 (Flare Connection)
VP25
External Dia. 32
(
)
Internal Dia. 25
46
44/42/40
44/42/40
Fuse.
Electronic Expansion Valve
R-410A PA Series
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
247
7