High Efficiency Filter
Specification
Model
Items
Filter Chamber
Dimension (W×D×T)
(mm)
Average Dust
Collection Efficiency
(%)
Initial Pressure Loss
(Pa)
Final Pressure Loss
(Pa)
Filter
Life Time (h)
Seats Structured
Applicable Models
Note:
The filter chamber is separately required when the high efficiency filter will be installed.
Characteristics of filter
KAFJ372L280,KAFJ373L280
Dimensions of filter
KAFJ372L280, KAFJ373L280
310
65% type
KAFJ372L280
KDJ3705L280
684×445×60
Colorimetric method 65%
27
42
98
Non-woven fabric of synthetic fiber
2500 hours (dust density 0.15mg/m³)
2
200·250
Class
KAFJ373L280
KDJ3705L280
684×445×60
Colorimetric method 90%
29
Non-woven fabric of synthetic fiber
1800 hours (dust density 0.15mg/m³)
Installation
Meet the airflow direction and arrow mark putting on
the High efficiency filter.
It is impossible to be built in with the air cleaning unit
together.
: http://splitoff.ru/tehn-doc.html
ED34-862
90% type
45
98
2
200·250
Class
FXMQ-MA