3.4.3. Network Type Output

Select this type, when the output will activate a network device (panel/repeater number).
Press MORE button to access the additional settings for
the network type output. All introduced changes must be
confirmed with APPLY button.

3.4.4. Action Type Output

Select this type, when in case of activation of input logic, the output has to perform an action type of event. Press
MORE button to access the list with action events. All introduced changes must be confirmed with APPLY button.
Press the active button for the respective action event.
The selected action event is automatically set into the
FUNCTION section.
iRIS8 - Addressable Fire Alarm Panel – Installer Programming
Introduce the settings for network type output:
- INPUT NUMBER. Enter a number of an input from 1 to
250.
- PANEL/REPEATER NUMBER. Enter a number of
panel or repeater from 1 to 64.
The possible action events for activation of the output are
listed after pressing the active button for FUNCTION
selection:
- SILENCE BUZZER - The output will perform a silencing
the buzzer in the system.
- SILENCE ALARM - The output will perform a silencing
sounders in the system.
- RESET - The output will perform a reset of the system.
- EVACUATE - The output will perform an evacuation in
the system.
- DELAY OVERRIDE - The output will perform an
override event in the system.
- CLASS CHANGE - To use the class change function,
connect the terminals of a switch with normally open
contacts to a module terminal. The output will perform
turning on the switch. The sound tone for class change
function is set in SOUNDERS MODE menus, item 3.5.4.
- SILENCE ALARM (STROBE ON) - The output will
perform a disablement of the sounders during evacuation
event, for example, when using the panel together with a
separate Voice Evacuation System. The sounders will be
silent, but their LED signalization will be active (WSST,
WSST IS, BSST and BSST IS) regardless their individual
settings.
- DAY MODE - The output will perform a switching to
DAY Operation mode.
- NIGHT MODE - The output will perform a switching to
NIGHT Operation mode.