Input/Output Module - Teletek electronics SIMPO Basic Information

Fire alarm panel
Hide thumbs Also See for SIMPO:
Table of Contents

Advertisement

D
:
0
3
2
L : 2
_
_
_
_
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Delays are the same as the sounder delays.

- Input/output module

D : 0 3 2
L : 2
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I N P U T
1
The buttons for setting the inputs and outputs conditions will change respectively to the
type of the MIO module. For example the table above is showing MIO22 (2 inputs, 2 outputs).
If we have MIO40 we will have 4 input buttons and if MIO04, we will have 4 Outputs buttons.
The settings for input 1 and 2 are identical, also Output 1 and Output 2 have identical settings.
Down below are shown only input 1 and output 1 settings.
- Inputs - The initial programming for each input is NONE – it means it does not
generates or triggers something:
G E N E R A T E S :
First event is FIRE:
G E N E R A T E S :
D E L A Y :
6 0 0
The device will generate fire from it's own zone. (This correspond to the sounders modes – if
there are addressable sounders in the same zone and they are in zonal activation they will
start, also if there are sounders in different zones with common activation they will activate
also).
The Generates can be changed with the up down arrows. With the right and left arrows
can be switched between the changeable fields (Generates and Delay).
Each input can have Delay up to 600 s.
The behaivior can be Latched. However it depends on the Event which is generated (it is
shown in the table below).
All events and types are placed in the table below:
Page 24 of 48
Simpo Addressable Panel
SIMPO - BASIC INFORMATION
S O U N D E R
M I O
I N P U T
2
N O N E
U s e
F I R E
G R O U P
Z O N E : 0 4
Z O N E : 0 4
O U T P U T
1
 
t o
s e l e c t
N A M E
L E D
B L I N K
N A M E :
O U T P U T
2