3. PROGRAMMING SYSTEM MENUS

Press in sequence SYSTEM - PROGRAMMING from Main Screen:
In general, the Programming menus of iRIS8 include
settings for zones, periphery and loop devices, types of
addressing loop devices, settings for inputs and outputs of
the panel.
The important network settings are previewed in Panel
menus.

3.1. Zones

Enter ZONES menu. The settings are distributed in two separate screens.
Press MORE button to move to the next screen.
Press APPLY button to save all introduced changes.
Fields description and available settings at ZONES menu:
Zone Number
Name
Zone Group Button
Mode
Sounder Delay (T2)
Fire Brigade Delay (T2)
Fire Protection Delay (T2)
Zone Status
Zone Sounders
Sounder Group A
Sounder Group B
Sounder Group C
iRIS8 - Addressable Fire Alarm Panel – Installer Programming
Use the left/right buttons to change the zone number. You can also directly enter the
number using the keyboard after selecting the digit button in the middle.
Active field for setting additional description/name for the selected zone number - up to 40
digits. Refer to item
2.3
for details about text introducing.
Attaching the zone to groups (item 3.1.1).
Active button for setting the operation mode of the zone (item 3.1.2).
Set time delay (0-540 sec.) for activation of Sounder (SND) panel output (item 3.1.3).
Set time delay (0-540 sec.) for activation of Fire Brigade (Fire R) panel output (item 3.1.3).
Set time delay (0-540 sec.) for activation of Fire Protection (Fire P) panel output (item
3.1.3).
Active button for changing operation status of the zone. Every pressing of the button
changes the operation status Enabled/Disabled. Every disabled zone is inactive and the
panel does not follow its state.
Note: After disablement of a zone, the system status LED DISABLE will light on at the front
panel and also will be generated message for that event.
Set the operation of the sounders associated to the respective zone number (item 3.1.4).
Enter a sounder group number from 1 to 127 according the system configuration.
Enter a sounder group number from 1 to 127 according the system configuration.
Enter a sounder group number from 1 to 127 according the system configuration.
Quick summery of the menus:
- Settings for Zones (item 3.1)
- Quick review of the zones' status by zone
number (item 3.1.5)
- Settings for Devices (item 3.2)
- Settings for Inputs (item 3.3)
- Settings for Outputs (item 3.4)
- Settings for the Panel (item 3.5)
- Restore to factory default settings (item 3.6)
- Save the system configuration (item 3.7)
All introduced changes must be confirmed with APPLY
button visible on the previous screen.
Press EXIT button to move back.