3.2.8.13. MIMIC Module

Available model:
SensoIRIS MIMIC – MIMIC/Repeater module with 32 LED indicators
The module has built-in isolator module, which must be connected during installation.
The module is specially designed for connection to mimic/repeater panels presenting a geographical plan of the fire
alarm system. The module is capable to control up to 32 LED outputs for indication of different events in the fire system,
and is provided also with special LED outputs for repeating a FIRE Alarm, Fault and Disablement events directly from
the fire alarm control panel.
For detailed description of the main screen of the device
see item 3.2.6. Press MORE button to access some
additional settings.
To configure the LED outputs operation, you have to go to menu OUTPUTS – see item 3.4. The "Output Pulse Type"
setting must be set as "CONTINUOUS" or "PULSED" (pulses with 500ms frequency).

3.2.8.14. GAS Detector

Available model:
SensoIRIS GAS Sense – gas detector
SensoIRIS GAS Sense is a gas detector designed for application in addressable fire alarm systems with IRIS fire alarm
panels. SensoIRIS GAS Sense is designed for detection of gas Methane and LPG. The detector is equipped with alarm
output for management of manipulator or electromagnetic valve (optional accessories).
For detailed description of the main screen of the device
see item 3.2.6. Press MORE button to access some
additional settings.
iRIS8 - Addressable Fire Alarm Panel – Installer Programming
The SensoIRIS MIMIC module must be powered on from
an external power supply unit 12-24VDC.
In case of external power supply failure, the fault
message "Power Supply Fault" will appear on the status
field of the device.
Alarm setting is for enabling/disabling the sounders,
when the detector is activated. Every pressing of the
button changes the setting.
- ENABLED. The sounders will be activated.
- DISABLED. The sounders remain silent in case of
activation of the detector. Press the "Apply" button to
save the settings.
35