3.3.1. Periphery Type Input

Select this type, when the input number is attached to an input terminal of the input-output main board.
Note: This is periphery device with address 2 and the installer can set only inputs from 1-4 – item 3.2.4.
Press MORE button to access the additional settings for
the periphery type input. Note that all introduced changes
must be confirmed with APPLY button in this main screen.

3.3.2. Loop Type Input

Select this type, when the input is an input terminal of a loop device. The devices with available inputs from the
SensoIRIS series are MIO-22, MIO-22M, MIO-40, MINP M.
Press MORE button to access the additional settings for
the loop type input. Note that all introduces changes must
be confirmed with APPLY button in this main screen.
Note: The modules with inputs SensoIRIS series - MIO-22, MIO-22M, MIO-40, MINP M - are displayed with the
available inputs. If the device is a detector, call point or a conventional zone module, the panel will show only one input
for it which is not available for programming.
Set the GROUP Number from 1-250, according the
system configuration. Next, set the periphery device
address, and number of the input terminal.
In this concrete case, the only available address is 2 (the
input-output main board module). You can set an input
number from 1 to 4, according the system requirements.
Press EXIT button to return to main screen.
Set the GROUP Number from 1-250, according the
system configuration. Next, set the loop device address,
loop number and number of the input terminal.
The available input numbers are displayed enclosed in
brackets.
The SABOTAGE option enables (ON setting) input
activation in case of fault condition. This will generate a
Fault type message for the output, where the input group
number is used.
The following messages on the screen may appear to
alert the installer for problems:
- "This device cannot be used as Input!" - That means
the device, or the set channel, cannot be used for
operation as input. The message will be displayed if the
set address is of a device type SensoIRIS MOUT, MIMIC,
MOUT-240, MIO-04.
- "Already used!" - That means the device, or the set
input, is already set for other operation into the system
configuration.