Examples for settings in PANELS submenu.
The receiving of messages for events is Enabled. The
options for repeating the outputs status are available for
further settings. Every pressing of the button will change
the status Enabled/Disabled.
Press APPLY button to save all introduced changes.
Examples for status in PANELS submenu.
New panel number is found in the network configuration.
Press ADD button. The status will change to PRESENT. If
there is set name for this panel it will be displayed into the
text field. Next step is to Enable the "Receiving" and
"Sending" control commands to other panels. Confirm with
APPLY button to save the settings.
IMPORTANT NOTES!
In case of making software or hardware Restore Defaults, the iRIS8 panel will restore the factory default
settings, including the Network Settings:
The Panel Number at Network Settings submenu is set by default as 1 - the installer must set the real number
of the panel in the network before enabling it – see item 3.5.2.1.
All connected panels will be recognised as NEW and must be added manually one-by-one in the PANELS
submenu.
The options for Receiving/Sending control commands and receiving/repeating of messages for events are
Disabled – the installer must enable all of them to restore the reporting from the other panels in the network
and the remote indication in case of events – see item 3.5.2.2.
The iRIS8 panel must be deleted from the rest panels in the network and ADDED again after all settings are
completed.
It is recommended, before making a Restore Defaults of any panel, to save its current system configuration as
TDF file using ProsTE specialized programming software. After software or hardware resetting, load the TDF back
to the panel and save time for introducing settings in menus. For details about ProsTE specialized programming
software ask your local distributer of the equipment.
iRIS8 - Addressable Fire Alarm Panel – Installer Programming
The receiving of messages for events is Disabled. The
options for repeating the outputs status are unavailable
for settings. Even if there are options set as Enabled, they
will be inactive and the panel will not repeat the status of
any of the outputs.
Press EXIT button to move back to previous screen.
The screen displays the information for the iRIS8 panel –
status THIS. No other settings for Receiving/Sending
commands or messages are available. Remember, the
Receiving/Sending commands and messages for events
for the iRIS8 itself can be done only via the other
connected panels in the network.