- SensoIRIS MOUT - The module has 1 potential output and is used for connection of conventional sounders.
Press active button with the name of the module to access the programming of the output. For setting the
activation of the output, refer to description of MIO04. Press MORE button to access the additional settings.
At the device settings screen the installer can review the general and set the additional parameter:
Sounder Group
Set a number of sounder group (1-127). Refer also to item
Review the current status of the output:
Output 1-4
- ON. The output is activated.
- OFF. The output is deactivated.
Note: The sounder group option is applicable for modules, when to one or more of its outputs are connected
conventional sounders and the "Sounders Mode" operation is set for the channel.

3.2.8.11. Zone Modules

Available model:
SensoIRIS MCZ – conventional zone module
The addressable SensoIRIS zone module has built-in isolator module, which must be connected during installation.
For detailed description of the main screen of the device
see item 3.2.6. Press MORE button to access some
additional settings.

3.2.8.12. 240V AC Relay Module

Available model:
SensoIRIS MOUT-240 – relay module for 240VAC interface
The module has built-in isolator module, which must be connected during installation.
For detailed description of the main screen of the device
see item 3.2.6. Press MORE button to access some
additional settings.
3.1.4
To save the new setting, press EXIT button to return to
the main screen of the device and press APPLY button
on the top of the screen.
The settings are the same as described for SensoIRIS
MOUT module.
34
for more details.