3.3.3. Zone Type Input

Select this type, when the input will be activated from a zone event. Press MORE button to access the additional
settings for the zone type input. Note that all introduced changes must be confirmed with APPLY button in this main
screen.
Press the active button for the respective zone event. The
selected zone event is automatically set into the
FUNCTION section at the main screen.

3.3.4. Alarms Type Input

Select this type, when the input will be activated from an encountered number of alarms from a zone number.
Press MORE button to access the additional settings for
the alarms type input. Note that all introduced changes
must be confirmed with APPLY button in this main screen.
iRIS8 - Addressable Fire Alarm Panel – Installer Programming
Set the GROUP Number from 1-250, according the
system configuration. Next, set the zone number from 1
to 200.
The possible zone events for activation of the input are
listed after pressing the active button for FUNCTION
selection:
- ZONE FIRE – The activation is in case of fire alarm
event in the set zone number.
- ZONE FAULT – The activation is in case of fault event
in the set zone number.
- ZONE DISABLED – The activation is in case of
disabling the set zone number.
- ZONE PREALARM – The activation is in case of fire
prealarm event in the set zone number.
Set the GROUP Number from 1-250, according the
system configuration. Next, set the zone number from 1
to 200.
In ALARMS COUNTER field enter a number (1-9) of
registered fire alarms, when after reaching their count, the
input will be activated.