Manual Call Points; Wall Mounted Sounders - Teletek electronics iRIS8 Engineer Programming Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

3.2.8.4. Manual Call Points

Available models:
SensoIRIS MCP150 - manual call point, indoor mounting, plastic case, red
SensoIRIS MCP150 IP67 - manual call point, outdoor mounting, plastic case, red
SensoIRIS MCP150 MR - manual call point, indoor mounting, metal case, red
SensoIRIS MCP150 PR - manual call point, indoor mounting, plastic case, red
SensoIRIS MCP150 PB - manual call point, indoor mounting, plastic case, blue
Note: All available models call points have same programming parameters. The system name for all of them is
SensoIRIS MCP150 without added abbreviates. The addressable SensoIRIS call point have built-in isolator module,
which must be connected during installation.
For detailed description of the main screen of the device
see item 3.2.6. Press MORE button to access some
additional settings.
At the device settings screen the installer can review the general and set one additional parameter:
Every pressing of the button alternatively changes the type of the event generated with
activation of the manual call point:
- EVACUATE. Immediate evacuation of the protected sites. The sounders will be activated
Event
immediately, as the set time delays Т1 and Т2 are ignored.
- ALARM. The manual call point operated as an automatic detector. The set time delays
Т1 and Т2 are active.

3.2.8.5. Wall Mounted Sounders

Available models:
SensoIRIS WSOU – sounder, red (available also in white)
SensoIRIS WSOU IS – sounder with built-in isolator module, red (available also in white)
For detailed description of the main screen of the device
see item 3.2.6. Press MORE button to access some
additional settings.
At the device settings screen the installer can review the general and set the additional parameters:
Every pressing of the button alternatively changes the sound level between HIGH/ LOW,
as this depends on the number of the connected sounders to the loop:
- HIGH. Set in those cases when the number of the connected sounders to the loop is up
Sound Level
to 30 (sounders WSOU, WSST, WSOU IS and WSST IS).
- LOW. Set in those cases when the number of the connected sounders to the loop is up to
60 (sounders WSOU, WSST, WSOU IS and WSST IS).
Sounder Group
Set a number of sounder group (1-127). Refer also to item
iRIS8 - Addressable Fire Alarm Panel – Installer Programming
To save the new setting, press EXIT button to return to
the main screen of the device and press APPLY button
on the top of the screen.
To save the new setting, press EXIT button to return to
the main screen of the device and press APPLY button
on the top of the screen.
27
3.1.4
for more details.