Table of Contents

Advertisement

3.4. Outputs

Enter OUTPUTS menu.
By default, all Outputs are set as NONE Type.
Use the arrow buttons, or enter an output number from 1
to 250. Press the active button for selection the output
type (NONE). Note: The screen content may change
according the settings for Output Type.
This type is selected, when the output is an output terminal of the main input-output module
Periphery
of the panel.
This option is selected, when the output is an output terminal of a loop device, as MIO-22,
Loop
MIO-22M, MIO-04, MOUT, MIMIC, etc.
This option is selected, when the output will be activated from a network device
Network
(panel/repeater number).
Action
This option is selected, when the output will be activated from an action event.
Event
This option is selected, when the output will be activated from a general type event.
NONE
The output is not used.
All Output types have some common settings available in the main settings screen. The settings are described in the
following table:
This is an active text field for description for the output up to 40 symbols. For text entering
Note
see item 2.3.
This setting is for behaviour of the output in case of activation. Every pressing of the button
changes the setting.
Behavior
LATCHED - Once activated, the output stays active until RESET.
UNLATCHED - Monitors the status.
Output Polarity
This setting is for the output active status. Every pressing of the button changes the setting.
(Available for
- NORMAL - The output will switch on when receiving of activation signal (event) and will
Periphery and
switch off when the signal is lost.
Loop type outputs
- INVERTED - The output will switch on when the signal is lost and will switch off when
only.)
receiving of activation signal (event).
Delay
Set a time delay for activation of the output within the interval 0–600 sec.
Set a Pulse type for operation of the output. The option is selected from a list after pressing
the active button next to the field.
- CONTINUOUS - The output signal is continuous.
- PULSED - The output signal is a pulse signal (3 sec. ON / 3 sec. OFF).
Output Pulse
- ONE PULSE - The output signal is a pulse with a programmable duration from 0 to 250
Type
seconds. The time is set in PULSE DURATION field, available for settings, when this option
is selected see item 3.4.2.
Note: ONE PULSE must be used in the case of ACTION type activating input or else the
activating input must be LATCHED or the output LATCHED.
This is a special menu for programming logic operations for activation of outputs - see item
Edit Outputs Map
3.4.6.
iRIS8 - Addressable Fire Alarm Panel – Installer Programming
The different output types are available for section in a
list. The type, as the other specific settings must be
confirmed in the main screen with APPLY button. Select
the output type to load the specific parameters for setting.