At the device settings screen the installer can review the general and set the additional parameters:
Every pressing of the button alternatively changes the sound level between HIGH/ LOW,
as this depends on the number of the connected sounders to the loop:
- HIGH. Set in those cases when the number of the connected sounders to the loop is up
Sound Level
to 30 (sounders BSOU, BSST, BSOU IS and BSST IS).
- LOW. Set in those cases when the number of the connected sounders to the loop is up to
100 (sounders BSOU, BSST, BSOU IS and BSST IS).
Sounder Group
Set a number of sounder group (1-127). Refer also to item

3.2.8.8. Bases with Sounder and Strobe

Available models:
SensoIRIS BSST – base with sounder and strobe
SensoIRIS BSST IS – base with sounder and strobe with built-in isolator mode
For detailed description of the main screen of the device
see item 3.2.6. Press MORE button to access some
additional settings.
At the device settings screen the installer can review the general and set the additional parameter:
Press to choose from a list the mode of operation of the sounder – see the screen below.
Mode
Every pressing of the button alternatively changes the sound level between HIGH/ LOW,
as this depends on the number of the connected sounders to the loop:
- HIGH. Set in those cases when the number of the connected sounders to the loop is up
Sound Level
to 30 (sounders BSOU, BSST, BSOU IS and BSST IS).
- LOW. Set in those cases when the number of the connected sounders to the loop is up to
100 (sounders BSOU, BSST, BSOU IS and BSST IS).
Sounder Group
Set a number of sounder group (1-127). Refer also to item
Press the button next to Mode field, to select the operation mode of the sounders:
Important notes!
The disablement of sounder with bases type BSOU, BSOU IS, BSST and BSST IS) will not affect the operation
of the mounted to it addressable detector.
The automatic detectors mounted to bases BSOU, BSOU IS, BSST and BSST IS are assigned at separate
addresses in the control panel!
for sounders' consumption summery and calculation.
See also
APPENDIX E
iRIS8 - Addressable Fire Alarm Panel – Installer Programming
To save the new setting, press EXIT button to return to
the main screen of the device and press APPLY button
on the top of the screen.
- Strobe lamp. Only the strobe light is active in case of
fire alarm event.
- Sound. Only the sound is active in case of fire alarm
event.
- Sound/Strobe. Both the strobe light and sound are
active in case of fire alarm event.
29
3.1.4
for more details.
3.1.4
for more details.