iRIS8 - Addressable Fire Alarm Panel – Installer Programming
At the device settings screen the installer can review the general and set some additional parameters:
Press the "Check" button to enter in a new screen to review the following parameters:
- Smoke [%]: Shows in percent the current level of smoke in the detector's smoke
chamber.
- Pollution [%]: Shows in percent the current level of pollution in the detector's smoke
Smoke [%] /
Temperature [°C]
chamber.
- Threshold for fire [°C] – Shows the operating temperature of the detector, in degrees
centigrade.
- Temperature [°C] – Shows the current temperature in the room, in degrees centigrade.
Setting a Device Group number for controlling a LED remote indicator (RI) – see the details
Device Group
in item 3.2.8.1.
Set here the sensitivity level of the optical-smoke part (S) of the detector and enable/
disable the heat part (T). These settings are valid for the daytime:
- Sensitivity level. There are 4 levels for setting of alarm level sensitivity for the optical-
smoke part: High, Normal, Middle and Low*.
Day Alarm Level
- Heat part. In addition, for this device only, the installer can enable or disable the heat part
of the detector. The state of the heat part can be changed with pressing the button.
The class temperature of SensoIRIS M140 and SensoIRIS M140 IS detectors is fixed on
A1R (58º, RoR).
Set here the sensitivity level of the optical part of the detector and enable/ disable the heat
Night Alarm Level
part. These settings are valid for the nighttime. Operation of setting is the same with those
for the day alarm level.
* NOTE: The currently set alarm level is displayed with small asterisk sign at the end of the field.
To change the level of sensitivity, simple press the active button next to the field and choose a new level from the list.
Attention: It is not allowed disabling the temperature and the optical parts at the same time!
If the optical-smoke part is disabled and the temperature part is set also to disabled, the setting for the optical-smoke
part will change automatically to enabled at high sensitivity level.
To save the new setting, press EXIT button to return to the
main screen of the device and press APPLY button on the
top of the screen.
There is an additional option for combined type fire
detectors – disabling the optical-smoke part.