APPENDIX E - SensoIRIS Sounders Consumption

Tables: Calculation of the consumption of SensoIRIS sounders.
To calculate the total consumption of the sounders in the loop and to define the proper sound level, you can use the
Table a below, as fill in the number of the used sounders according their type.
Table 1 for calculation of the total consumption of the sounders in the loop with defined sound level and set ALARM
and/or EVACUATE TONE type 27 (see item
Sounder
Number
WS
WS IS
WSOU
WSOU IS
WSST
WSST IS
BSOU
BSOU IS
BSST
BSST IS
Table 2 for calculation of the total consumption of the sounders in the loop with defined sound level and set ALARM
and/or EVACUATE TONE other type sound (see item
Sounder
Number
WS
WS IS
WSOU
WSOU IS
WSST
WSST IS
BSOU
BSOU IS
BSST
BSST IS
3.5.4
HIGH
Sound Level
____ x 16,5mA
___ x 16,5mA
____ x 16,5mA
____ x 16,5mA
____ x 22mA
____ x 22mA
____ x 10mA
____ x 10mA
____ x 10mA
____ x 10mA
Consumption of the sounders in the loop:
HIGH
Sound Level
____x 10mA
___ x 10mA
____ x 10mA
____ x 10mA
____ x 16,5mA
____ x 16,5mA
____ x 10mA
____ x 10mA
____ x 10mA
____ x 10mA
Consumption of the sounders in the loop:
iRIS8 - Addressable Fire Alarm Panel – Installer Programming
Sounders Mode):
LOW
Sound Level
____ x 5mA
___ x 5mA
____ x 5mA
____ x 5mA
____ x 12mA
____ x 12mA
____ x 3mA
____ x 3mA
____ x 3mA
____ x 3mA
3.5.4
Sounders Mode):
LOW
Sound Level
____ x 4mA
___ x 4mA
____ x 4mA
____ x 4mA
____ x 11mA
____ x 11mA
____ x 3mA
____ x 3mA
____ x 3mA
____ x 3mA
83
Total consumption, mA
(HIGH + LOW)
Total consumption, mA
(HIGH + LOW)