iRIS8 - Addressable Fire Alarm Panel – Installer Programming
Earth Fault function DISABLED
Sounder Disabled
Fire Brigade Output Disabled
Fire Protection Output Disabled
Fault Output Disabled
Zone In Test
Transmitting device active
Extinguishing output active
Sirens active
User log off
Installer log off
User log on
Installer log on
High Resistance Disabled
Total loss of Power
Buzzer Disabled
Network Fault
Loop Device Disabled
Chamber Fault
Clean Me Now
Loop Device Input Fault
Loop Device Output Fault
Alarm
PreAlarm
Test Alarm
Loop Device Type Error
Loop Device Fault
Double Address
Evacuate
Log Fault
Gas Alarm
Power Supply Fault
Panic
Active Relay
Loop Device Input Active
Loop Device Output Active
Activated Output
Redundant processor fault
Type Error
External Power Supply Fault
The Earth Fault indication is disabled.
The Sounders are disabled.
The fire output is disabled.
The extinguishing output is disabled.
The fault output is disabled.
The zone is in test mode.
The Fire output is activated.
The Extinguishing output is activated.
The sounders are activated.
Exit from access level 2 (Maintenance).
Exit from access level 3 (Installer).
Entry in access level 2 (Maintenance).
Entry in access level 3 (Installer).
The indication for high battery resistance is disabled.
Both main and backup power supply are lost (the main power supply is lost and
the accumulator battery is fully discharged).
The internal buzzer is disabled.
Redundant network breakdown.
The loop device is disabled.
Fault in the detector.
Dirty detector chamber.
Fault in loop device input.
Fault in loop device output.
Fire alarm signal from detector.
Fire alarm signal from detector in 2DEVICES or DOUBLE operation mode for
zone.
Fire alarm signal from tested detector.
A different than the expected type of device has been detected at the address.
The device does not respond (lost or damaged).
More than one device with the same address in the loop.
Activated Call Point or EVACUATE button on the panel.
The Log file event is lost or damaged.
Activated gas detector SensoIRIS GAS.
Fault in the external power supply of conventional zone module SensoIRIS MC-Z
or gas detector SensoIRIS GAS.
Panic alarm signal from detector.
Activated relay output of the panel. After the message is displayed also the
number of the activated relay (1-4).
Activated input of a loop device.
Activated output of a loop device.
Activated output of the panel.
Redundant processor is failed.
SensoIRIS MIO22M module. Wrong type of the output is detected. That means
that a jumper is set or removed when the power supply of the module is ON. The
fault will be cleared with switching off the power supply of the module, including
the external power supply unit, and switching it on again.
SensoIRIS MIO22M module. Missing or low external power supply. The fault is
cleared when the normal power supply is restored.