Set Address - Teletek electronics iRIS8 Engineer Programming Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Enter ADDRESSING menu. The menu includes the following submenus:
During any of the ADDRESSING procedures the iRIS8 panel enters in a special operation mode for addressing devices
- the panel is busy and does not follow the operation of the other devices in the system. The addressing mode is
visualizing with an icon of a "rotating arrows circle". The menus for reviewing of Alarms, Faults, Warnings, Tests and
Disablements are inactive.

3.2.9.1. Set Address

In this submenu the installer can directly set addresses to new devices in the system. The procedure is same with that
for self-addressing. It is suitable when the installer needs to add single devices to the system configuration at free
addresses. The detectors and sounders must not be mounted to the bases; the call points and modules must not be
connected to the loop.
To set address to a new device, enter in the installer's menu - ADDRESSING - SET ADDRESS. The device must be
prepared for connection to the panel.
The system automatically shows the first address in the
system. If the address is assigned, the panel will display
the device with its system name. You can check the
position of the device assigned at this address with
pressing the TURN ON button - the device LED(s) will light
on permanently. Next pressing of the same button will off
the LED(s).
During the setting of the address the system is idle for
operation. The blinking system icon shows that the
process is running on.
iRIS8 - Addressable Fire Alarm Panel – Installer Programming
• Set Address
• Change Address
• Start Self-Addressing
• Autoaddressing
• Loop Zero Address
Use the arrow buttons to scroll over addresses and loop
numbers. Choose an address number. The address is
FREE for use, if APPLY button is active in the left bottom
corner. Take the new device and connect it to the system
- mount the detector or siren to the base or connect the
module to the loop. Press the APPLY button and wait for
a couple of seconds.
If the addressing is successful, the message
SUCCESSFUL is shown on the screen. The panel enters
in reset mode. You can proceed with setting the next
address or escape with EXIT button.
If the message is ERROR, then there is a problem - the
device is not properly connected; there is no
communication with the panel.
37

Advertisement

Table of Contents
loading

This manual is also suitable for:

Iris8 sIris8 extIris8 b

Table of Contents