4.11. View Insulator Active

This is an information menu for reviewing the active insulators (built-in isolator in SensoIRIS devices).
Enter MAINTENANCE – VIEW INSULATOR ACTIVE menu.
Routine Maintenance
iRIS8 S and iRIS8 B control panels do not require any specific maintenance. To clean the panel's surface, use a dry
cloth. Detergents or solvents should not be used to clean the panel and care must be taken that water does not enter
the enclosure.
The control panels contain sealed lead acid batteries (24V/18Ah) to provide standby power in the event of mains failure.
This battery has a life expectancy of around 4 years. It is recommended that this battery be annually tested in
accordance with the battery manufacturer's recommendations to determine its suitability for continued standby
applications.
Routine testing of the fire alarm system in accordance with EN54-14 will identify any malfunction of the control panel
and any malfunction should be reported to the fire alarm maintenance company immediately.
Detection devices are automatically calibrated on a daily basis and any devices that fail the detector manufacturer
requirements will be notified as a maintenance fault. The contamination status menu is also useful in determining
detection devices that are approaching their working range limits.
The active insulators in the system are displayed as
device addresses in the field under the respective loop
number.