Periphery Type Output; Loop Type Output - Teletek electronics iRIS8 Engineer Programming Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

iRIS8 - Addressable Fire Alarm Panel – Installer Programming

3.4.1. Periphery Type Output

Select this type, when the output number is attached to an output terminal of the input-output main board.
Note: This is periphery device with address 2 and the installer can set only the relay outputs from 1-4 – item 3.2.4.
Press MORE button to access the additional settings for
the periphery type output. All introduced changes must be
confirmed with APPLY button.

3.4.2. Loop Type Output

Select this type, when the output is an output terminal of a loop device. The devices with available outputs from the
SensoIRIS series are MIO-22, MIO-22M, MIO-04, MOUT, MOUT-240, MIMIC.
Press MORE button to access the additional settings for
the loop type output. All introduced changes must be
confirmed with APPLY button.
In case, for the output is set ONE PULSE option for
operation, the duration of the single pulse is available for
setting after pressing MORE button.
Note: The modules with outputs SensoIRIS series - MIO-22, MIO-22M, MIO-04,
MOUT, MOUT-240, MIMIC - are displayed with the available outputs. If the device is
a sounder, the panel will show only one output for it and it is not programmable.
The following messages on the screen may appear to alert the installer for
problems:
- "This device cannot be used as Output!" - That means the device, or the set
channel, cannot be used for operation as output. The message will be displayed if the
set address is of a device type SensoIRIS MINP M, MIO-40, detector or call point.
- "Already used!" - That means the device, or the set output, is already set for other
operation into the system configuration.
50
The only available address for periphery device is 2 (the
input-output main board module). You can set an output
relay number from 1 to 4, according the system
requirements and configuration. Press EXIT button to
return to main screen.
Set the loop device address, loop number and number of
the output terminal. The available output numbers are
displayed enclosed in brackets. Confirm the settings with
APPLY button. Press EXIT button to return to main
screen.
The Pulse duration is set from 0 to 250 seconds after
pressing the active button.