Teletek electronics iRIS8 Engineer Programming Manual page 33

Addressable fire alarm control panel
Table of Contents

Advertisement

- SensoIRIS MIO22M - The module has 2 inputs and 2 monitored outputs, programmable for activation by an
event. Every of the outputs can be set to operate as monitored or non-monitored type, as the setting is via
jumpers on the module's PCB. The active state of the monitored outputs can be programmed for operation in
Normal or Inverted mode with configuration in menu OUTPUTS - see item 3.4. When an output is set to operate
as Monitored, it must be powered on from an external power supply unit (18-30VDC).
Press active button with the name of the module to access the programming of the outputs and inputs. For
setting the activation of the inputs, refer to description of MIO40, and for setting the activation of outputs, refer
to description of MIO04. Press MORE button to access the additional settings.
Description of OUTPUT 1 and OUTPUT 2 operation type:
- NonMonitored. The OUTPUT is set to operate as Not Monitored type - no jumper is set on the PCB;
- Monitored. The OUTPUT is set to operate as Monitored type - a jumper is set on the PCB.
- Type Error. Wrong type of the output is detected. That means a jumper is set or removed when the powers supply of
the module is ON. The fault will be cleared with switching off the power supply of the module, including the external
power supply unit, and switching it on again.
- Power Supply fault. Missing or low external power supply. The fault is cleared when the normal power supply is
restored.
Attention: The jumpers for setting of Monitored operation type must be set or removed ONLY with power
supply OFF of the module, including the external power supply! If the jumper is set or removed with power
supply on, the operation type of the module will change to "Type Error"!
The status of OUTPUT 1 and OUTPUT 2 can be one of the following:
- ON. The OUTPUT is activated.
- OFF. The OUTPUT is deactivated.
- OPEN. The line connected to the output is open or no EOL module is connected to the terminal in case the output is
not used.
- SHORT. There is a short-circuit in the line connected to the output. In case of short-circuit at energized monitored
output, the power of the output will be off until the normal operating condition is restored.
In case of a fault condition at modules' outputs its status is changed to "IO Fault". Press the MORE button to review the
type of the fault. The module will return to Normal state when the fault is restored. At the example below the "OI Fault"
state is caused from Type Error condition - the jumper of Output 2 has been set or removed without switching off the
power supply of the module.
iRIS8 - Addressable Fire Alarm Panel – Installer Programming
33